TSCA Disposal Requirements for Flourescent Light Ballasts
| PCB Capacitor | PCB Potting Material | Labeling, Transportation and Manifesting for Disposal | Disposal Reference in §761 | Disposal Options |
| "No PCBs" label | Not Regulated under TSCA | N/A | Not Regulated under TSCA | |
| None | < 50 ppm | Not Regulated under TSCA | N/A | Not Regulated under TSCA |
| Intact and non-leaking or none | >= 50 ppm | Is a PCB bulk product waste. No labeling is required. Manifesting is required for disposal in accordance with §761.61(a); is not required under §761.62(b); may be required under §761.20(c). | .50(b)(2)(ii) .62(a)-(c) |
TSCA Incinerator, TSCA/RCRA Landfill, Alternate Destruction Method, Decontamination (§761.65(d) storage approval may be required), Coordinated approval, State approved landfill (leach test required), Risk-based approval |
| Intact and non-leaking | < 50 ppm | No labeling of manifesting required | .50(b)(2)(i) .60(b)(2)(ii) |
As municipal solid waste. 40 CFR 761 subpart D options |
| Leaking | < 50 ppm or >= 50 ppm |
Disposal as PCB bulk product waste. No labeling is required. Manifesting is required for disposal in accordance with §761.62(a); may be required under §761.62(c). | .62(a) or (c) | TSCA Incinerator TSCA/RCRA Landfill Alternate Destruction Method. Decontimination (§761.65(d) storage approval may be required). Coordinated approval. Risk-based approval |